JOURNEYMAN ELECTRICIAN

Comprehensive Examination

Based on NEC 2023 & Electrical Theory
SunFusion Energy Systems Inc.
🎯 Interactive Version – Results Submitted Upon Completion

📋 Applicant Information (Required)

⚠️ Important: Your exam results will be automatically submitted to SunFusion Energy Systems upon completion. Please ensure your information is accurate.

📝 Examination Instructions

  • You may change your answers at any time before submitting the exam.
  • Click on any answer to select it. Click a different answer to change your selection.
  • Correct answers will NOT be shown until after you submit.
  • You must answer all 100 questions before submitting.
  • A score of 70% or higher is required to pass.
  • Results will be automatically emailed to SunFusion upon submission.
Answered
0/100
Remaining
100

📐 Reference Formulas

E = I × R P = E × I P = I² × R P = E² / R I = P / E VD = (2 × K × I × D) / CM
SECTION 1: ELECTRICAL THEORY & CALCULATIONS (Questions 1-20)
0/20
1.What is the total resistance of three 30-ohm resistors connected in parallel?
A) 90 ohms
B) 30 ohms
C) 10 ohms
D) 15 ohms
2.A 240V single-phase load draws 45 amperes. What is the power consumption in watts?
A) 5,400 W
B) 10,800 W
C) 18,720 W
D) 7,200 W
3.In a purely resistive AC circuit, the power factor is:
A) 0
B) 0.5
C) 0.8
D) 1.0
4.The voltage across a 20-ohm resistor with 5 amperes flowing through it is:
A) 4 volts
B) 25 volts
C) 100 volts
D) 500 volts
5.What is the line voltage in a 208V three-phase wye system?
A) 120V
B) 208V
C) 240V
D) 277V
6.A capacitor in an AC circuit causes current to:
A) Lead voltage by 90°
B) Lag voltage by 90°
C) Be in phase with voltage
D) Lag voltage by 45°
7.What is the phase-to-neutral voltage in a 480V three-phase wye system?
A) 208V
B) 240V
C) 277V
D) 480V
8.Two 60-ohm resistors in series have a total resistance of:
A) 30 ohms
B) 60 ohms
C) 120 ohms
D) 3,600 ohms
9.A 5 HP motor at 230V single-phase draws approximately how many amps? (Use 746W/HP)
A) 16.2 amps
B) 21.7 amps
C) 28.0 amps
D) 32.4 amps
10.What is the power dissipated by a 100-ohm resistor with 2 amps flowing through it?
A) 50 watts
B) 200 watts
C) 400 watts
D) 800 watts
11.The unit of electrical capacitance is the:
A) Henry
B) Farad
C) Ohm
D) Coulomb
12.In a delta-connected three-phase system, line current equals:
A) Phase current
B) Phase current × 1.414
C) Phase current × 1.732
D) Phase current ÷ 1.732
13.A circuit has 30 ohms resistance and 40 ohms reactance. What is the impedance?
A) 50 ohms
B) 70 ohms
C) 10 ohms
D) 1,200 ohms
14.One kilowatt-hour (kWh) equals:
A) 1,000 watts for 1 second
B) 1,000 watts for 1 hour
C) 100 watts for 10 hours
D) Both B and C
15.An inductor opposes changes in:
A) Voltage
B) Resistance
C) Current
D) Frequency
16.Using NEC Chapter 9 Table 8 (K=12.9 for copper), what is the voltage drop for a 150-foot run of #10 AWG (10,380 CM) carrying 20 amps?
A) 2.5 volts
B) 3.1 volts
C) 3.7 volts
D) 4.8 volts
17.kVA stands for:
A) Kilo-Volts-Actual
B) Kilo-Volt-Amperes
C) Kilo-Variable-Amps
D) Kilo-Voltage-Average
18.A 15 kW heater at 240V single-phase draws how many amps?
A) 36 amps
B) 52.5 amps
C) 48 amps
D) 62.5 amps
19.Power factor is the ratio of:
A) True power to apparent power
B) Reactive power to true power
C) Voltage to current
D) Resistance to impedance
20.The formula for three-phase power is:
A) P = E × I
B) P = √3 × E × I × PF
C) P = 3 × E × I
D) P = E² / R
SECTION 2: NEC CODE REQUIREMENTS (Questions 21-40)
0/20
21.Per NEC 210.8, GFCI protection is required in dwelling unit bathrooms for receptacles rated:
A) 15 amps only
B) 20 amps only
C) 125V, 15 and 20 amp
D) All receptacles regardless of rating
22.NEC 210.52 requires kitchen countertop receptacles to be placed so that no point is more than how far from a receptacle?
A) 12 inches
B) 24 inches
C) 36 inches
D) 48 inches
23.Per NEC 240.4(D), the maximum overcurrent protection for #14 AWG copper is:
A) 15 amps
B) 20 amps
C) 25 amps
D) 30 amps
24.According to NEC 314.16, what is the volume allowance for a #12 AWG conductor?
A) 2.0 cubic inches
B) 2.25 cubic inches
C) 2.25 cubic inches
D) 2.5 cubic inches
25.NEC 250.66 requires the grounding electrode conductor for a 400-amp service with 500 kcmil copper conductors to be minimum:
A) #8 AWG copper
B) #6 AWG copper
C) #4 AWG copper
D) #1/0 AWG copper
26.Per NEC 300.4(A)(1), where cables pass through bored holes in wood framing, the edge of the hole must be at least how far from the nearest edge of the wood member?
A) 1 inch
B) 1-1/4 inches
C) 1-1/2 inches
D) 2 inches
27.NEC 404.2(C) requires switches controlling lighting loads to:
A) Have a grounded conductor (neutral) at the switch location
B) Be rated for 20 amps minimum
C) Have GFCI protection
D) Be located within 6 feet of the fixture
28.Per NEC Table 310.16, what is the ampacity of #6 AWG THHN copper in a raceway at 30°C ambient?
A) 55 amps
B) 65 amps
C) 75 amps
D) 85 amps
29.NEC 210.12 requires AFCI protection for dwelling unit:
A) Kitchens only
B) Bedrooms, living rooms, and similar areas
C) Bathrooms only
D) Garages only
30.Per NEC 230.79, the minimum service disconnecting means rating for a single-family dwelling is:
A) 60 amps
B) 75 amps
C) 80 amps
D) 100 amps
31.NEC 250.52(A)(1) requires a metal underground water pipe electrode to be in contact with earth for at least:
A) 10 feet
B) 8 feet
C) 6 feet
D) 5 feet
32.Per NEC 430.52, the maximum branch circuit short-circuit protection for a motor using an inverse time breaker is typically:
A) 125% of motor FLC
B) 175% of motor FLC
C) 250% of motor FLC
D) 300% of motor FLC
33.NEC Article 680 requires pool pump motors to be protected by:
A) AFCI
B) GFCI
C) Surge protector
D) Time delay fuse only
34.Per NEC 422.11, the branch circuit rating for a 1,500W, 120V appliance must be at least:
A) 15 amps
B) 20 amps
C) 25 amps
D) 30 amps
35.NEC 314.27(A)(2) requires ceiling outlet boxes supporting luminaires over 50 pounds to:
A) Use a standard 4-inch square box
B) Be mounted to a joist only
C) Have GFCI protection
D) Be listed and identified for the weight
36.Per NEC 334.80, the ampacity of NM cable is based on the _____ conductor temperature rating.
A) 60°C
B) 75°C
C) 90°C
D) 105°C
37.NEC 408.36 requires panelboard circuits to be protected by:
A) Fuses only
B) An overcurrent device with a rating not greater than the panelboard rating
C) Circuit breakers rated at 125% of the panelboard rating
D) Ground fault protection only
38.Per NEC 210.52(G), dwelling unit garages require at least:
A) One receptacle outlet
B) Two receptacle outlets
C) One receptacle per vehicle space
D) No receptacles required
39.NEC 250.118 recognizes which of the following as an equipment grounding conductor?
A) RMC (Rigid Metal Conduit)
B) IMC (Intermediate Metal Conduit)
C) EMT (Electrical Metallic Tubing)
D) All of the above
40.Per NEC 220.12, the general lighting load for dwelling units is calculated at:
A) 2 VA per square foot
B) 2.5 VA per square foot
C) 3 VA per square foot
D) 3.5 VA per square foot
SECTION 3: WIRING METHODS & MATERIALS (Questions 41-55)
0/15
41.EMT (Electrical Metallic Tubing) is secured per NEC 358.30 within _____ of each outlet box.
A) 2 feet
B) 3 feet
C) 4 feet
D) 5 feet
42.Per NEC 312.6(A), the minimum depth of a pull box for straight pulls with 2-inch conduit is:
A) 16 inches
B) 12 inches
C) 10 inches
D) 8 inches
43.NM cable (Romex) is permitted in:
A) Commercial buildings over 3 floors
B) Wet locations
C) One and two-family dwellings
D) Direct burial applications
44.Per NEC Table 1, Chapter 9, the maximum conduit fill for 3 or more conductors is:
A) 31%
B) 53%
C) 60%
D) 40%
45.The color required for an ungrounded (hot) conductor in a 208Y/120V system, Phase B is:
A) Black
B) Any color except white, gray, or green
C) Orange (high-leg only)
D) Red only
46.Per NEC 300.5, the minimum burial depth for rigid metal conduit (not under a building) is:
A) 6 inches
B) 12 inches
C) 18 inches
D) 24 inches
47.MC cable must be supported per NEC 330.30 at intervals not exceeding:
A) 4 feet
B) 4.5 feet
C) 6 feet
D) 8 feet
48.Per NEC 358.10, EMT is NOT permitted in:
A) Concealed locations
B) Concrete walls
C) Dry locations
D) Where subject to severe physical damage
49.The high-leg conductor in a 4-wire delta system must be identified by which color?
A) Orange
B) Red
C) Blue
D) Yellow
50.Per NEC 376.22, the maximum number of conductors in a wireway is limited to _____ of cross-sectional area.
A) 10%
B) 20%
C) 40%
D) 50%
51.UF cable differs from NM cable primarily because it:
A) Has a metal armor
B) Is rated for higher temperatures
C) Is suitable for direct burial and wet locations
D) Uses larger conductors
52.Per NEC 344.30, RMC must be secured within _____ of each box or enclosure.
A) 3 feet
B) 4 feet
C) 5 feet
D) 6 feet
53.Per NEC 352.30, PVC conduit must be supported at intervals not exceeding:
A) 4 feet for all sizes
B) 6 feet for all sizes
C) 8 feet for all sizes
D) Varies by size per Table 352.30
54.The minimum bending radius for EMT per NEC 358.24 is:
A) 4 times the internal diameter
B) Per Table 2, Chapter 9 (varies by size)
C) 8 times the external diameter
D) 10 times the internal diameter
55.LFMC (Liquidtight Flexible Metal Conduit) is often used in:
A) Connections to motors and equipment subject to vibration
B) Underground installations only
C) High-temperature environments above 140°F
D) Service entrance conductors
SECTION 4: MOTORS & CONTROLS (Questions 56-70)
0/15
56.Per NEC 430.22, motor branch circuit conductors must have an ampacity of at least _____ of the motor FLC.
A) 100%
B) 115%
C) 125%
D) 150%
57.Motor overload protection is designed to protect the motor from:
A) Sustained overcurrent conditions during operation
B) Short circuits only
C) Ground faults only
D) Voltage fluctuations
58.The FLC for motor calculations must be taken from:
A) The motor nameplate
B) NEC Tables 430.247-430.250
C) The manufacturer's data sheet
D) Calculated from HP and voltage
59.A motor disconnecting means must:
A) Be within sight of the motor
B) Be capable of being locked in the open position
C) Open all ungrounded conductors
D) All of the above
60.Per NEC Table 430.248, the FLC for a 5 HP, 230V, single-phase motor is:
A) 28 amps
B) 32 amps
C) 40 amps
D) 50 amps
61.A VFD (Variable Frequency Drive) controls motor speed by:
A) Varying the resistance in the circuit
B) Changing the number of poles
C) Adjusting the frequency and voltage supplied
D) Mechanical gear reduction
62.Per NEC 430.32, motor overload protection for a motor with a service factor of 1.15 or greater is typically set at:
A) 115% of nameplate FLA
B) 125% of nameplate FLA
C) 130% of nameplate FLA
D) 150% of nameplate FLA
63.A three-phase motor will run in reverse if you:
A) Swap any two phase conductors
B) Reduce the voltage
C) Change the frequency
D) Remove the ground wire
64.A magnetic motor starter typically includes:
A) A contactor
B) Overload relays
C) Control circuit connections
D) All of the above
65.Star-delta (wye-delta) starting is used to:
A) Increase motor torque
B) Reduce starting current
C) Change motor direction
D) Increase motor speed
66.Per NEC 430.109, the motor disconnecting means for a 2 HP, 230V motor must be rated at least:
A) 100% of motor FLC
B) 110% of motor FLC
C) 115% of motor FLC
D) 125% of motor FLC
67.A holding contact (seal-in contact) on a motor starter:
A) Maintains the contactor coil energized after the start button is released
B) Provides overload protection
C) Reverses motor direction
D) Limits inrush current
68.Motor nameplate data does NOT typically include:
A) Horsepower rating
B) Recommended wire size
C) Service factor
D) Full load amps
69.A DOL (Direct On-Line) starter:
A) Reduces starting current
B) Provides soft start capability
C) Uses reduced voltage during starting
D) Applies full voltage immediately to the motor
70.The purpose of a jog button on a motor controller is to:
A) Provide emergency stop
B) Reset overload relays
C) Allow momentary operation for positioning
D) Change motor speed
SECTION 5: SOLAR PV & BATTERY STORAGE (Questions 71-85)
0/15
71.Per NEC 690.8, PV system circuit conductor ampacity must be at least _____ of the maximum circuit current.
A) 125%
B) 100%
C) 115%
D) 150%
72.A string inverter differs from a microinverter in that:
A) It converts DC to DC
B) It handles multiple panels in series (a string)
C) It mounts on each individual panel
D) It only works with battery systems
73.Per NEC 690.12, rapid shutdown of PV systems requires conductors more than _____ from the array to be reduced to 30V within 30 seconds.
A) 5 feet
B) 3 feet
C) 1 foot
D) 10 feet
74.LiFePO4 batteries are preferred over NMC batteries for residential ESS because they:
A) Have higher energy density
B) Are lighter weight
C) Cost less per kWh initially
D) Are more thermally stable and have longer cycle life
75.A hybrid inverter can:
A) Manage PV, battery, and grid connections simultaneously
B) Only convert AC to DC
C) Only work off-grid
D) Only charge batteries from the grid
76.Per NEC Article 706, ESS (Energy Storage Systems) installations require:
A) Only a main breaker
B) Disconnecting means and proper working space
C) Outdoor installation only
D) No special requirements
77.The open-circuit voltage (Voc) of a PV module:
A) Decreases significantly in cold temperatures
B) Remains constant regardless of temperature
C) Increases in cold temperatures
D) Is always equal to Vmp
78.Per NEC 690.41, PV systems over 30V must have:
A) A grounded conductor or ground fault protection
B) AFCI protection
C) Surge protection
D) GFCI protection
79.Battery State of Charge (SOC) indicates:
A) The battery's age
B) The charging current
C) The total capacity in kWh
D) The percentage of available capacity remaining
80.When sizing a backup battery system, the critical loads panel:
A) Must include all house loads
B) Contains only essential circuits for backup power
C) Cannot include any 240V circuits
D) Must be rated for 200 amps
81.MPPT (Maximum Power Point Tracking) in a charge controller:
A) Optimizes PV array output by adjusting voltage/current relationship
B) Tracks the sun's position
C) Monitors battery temperature only
D) Controls the grid connection
82.Per NEC 705.12, the maximum PV system output breaker for a 200A main panel using the 120% rule is:
A) 20 amps
B) 30 amps
C) 40 amps
D) 50 amps
83.Anti-islanding protection in grid-tied inverters:
A) Increases power output
B) Prevents the inverter from feeding the grid during an outage
C) Charges the battery faster
D) Reduces harmonic distortion
84.The temperature coefficient of a PV module affects:
A) Only the current output
B) Only the physical size
C) The mounting requirements
D) The maximum voltage calculations for string sizing
85.Per NEC 706.31, ESS disconnecting means must:
A) Disconnect all ungrounded conductors and be lockable
B) Only disconnect the positive conductor
C) Be located inside the battery enclosure
D) Be rated for 400 amps minimum
SECTION 6: SAFETY & TROUBLESHOOTING (Questions 86-100)
0/15
86.Before working on any electrical circuit, the FIRST step is to:
A) Put on safety glasses
B) De-energize and verify zero energy state
C) Notify your supervisor
D) Check the weather
87.A clamp-on ammeter measures current by:
A) Direct contact with the conductor
B) Measuring voltage drop across a shunt
C) Sensing the magnetic field around the conductor
D) Calculating from power and voltage
88.When troubleshooting a circuit with no power, you should check the _____ first.
A) Source/breaker
B) Load
C) Neutral connection
D) Ground wire
89.The primary purpose of PPE (Personal Protective Equipment) is to:
A) Meet OSHA requirements only
B) Make work more comfortable
C) Impress customers
D) Protect the worker from injury or illness
90.Bonding differs from grounding in that bonding:
A) Connects equipment to earth
B) Connects metal parts together to ensure electrical continuity
C) Is only required for service equipment
D) Uses larger conductors than grounding
91.Per OSHA 1910.333, electrical work should only be performed energized when:
A) De-energizing would create a greater hazard or is infeasible
B) The voltage is under 600V
C) The worker has 5+ years experience
D) The job is a rush project
92.The limited approach boundary for 480V per NFPA 70E is approximately:
A) 3 feet 6 inches
B) 5 feet
C) 10 feet
D) 15 feet
93.Arc flash PPE category is determined by:
A) Voltage alone
B) Worker's experience level
C) Distance from equipment
D) Incident energy from an arc flash hazard analysis
94.The difference between a ground fault and a short circuit is:
A) A ground fault involves current flow to ground; a short circuit is between conductors
B) There is no difference
C) A short circuit is less dangerous
D) A ground fault can only occur with DC
95.Per NEC 250.64(B), the grounding electrode conductor must be:
A) Always installed in PVC conduit
B) Protected where subject to physical damage
C) Minimum #4 AWG for all installations
D) Painted orange for identification
96.Lockout/Tagout (LOTO) procedures are designed to:
A) Mark completed work
B) Identify the worker assigned to a task
C) Prevent accidental re-energization during maintenance
D) Test circuit integrity
97.A megohmmeter (Megger) is used to test:
A) Current flow
B) Voltage levels
C) Continuity only
D) Insulation resistance
98.Before using a voltage tester, you should:
A) Test it on a known live source to verify it's working
B) Assume it's working if the battery is good
C) Check the manufacture date
D) Clean the probes with water
99.Per NEC 250.30, a separately derived system must be grounded at:
A) The main service panel only
B) The source of the separately derived system
C) Any convenient location
D) The load side only
100.Per NEC 200.7(C)(1), a white conductor can be used as an ungrounded conductor if:
A) It is never permitted
B) Only in 120V circuits
C) It is permanently re-identified at each termination point
D) Only in conduit installations

EXAMINATION COMPLETE

0/100 (0%)

Correct
0
Incorrect
0
Score
0%

💰 WAGE CALCULATION

SunFusion Energy Systems Inc. – Performance-Based Compensation

0%
--
$0.00

🔧 Conduit Bending Skill Assessment (Separate Evaluation)

⚡ This bonus is determined by a separate hands-on evaluation conducted by a supervisor.
Base Rate: $0.00 + Bending Bonus: $0.00 =
Total Hourly Rate
$0.00

📊 Wage Scale Reference

Score Range Classification Base Rate Formula
Below 50% Below Minimum Does not qualify
50-59% Entry Level / Trainee $18.00 - $24.36/hr
60-69% Apprentice I $24.40 - $30.16/hr
70-79% Apprentice II $30.80 - $36.56/hr
80-89% Journeyman $37.20 - $42.96/hr
90-94% Senior Technician $43.60 - $46.16/hr
95-100% Lead / Foreman $46.80 - $50.00/hr

Formula: $18.00 + (Score% - 50) × $0.64/hr

0